ConduitCount

How many #2 THHN fit in 4" Rigid?

442 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.1158 sq in per wire = 44.50, so 44.

44 #2 THHN in 4" Rigid, drawn to scale

This pull in numbers

44 wires fill
39.6 % of 4" Rigid
Limit for three or more
40 %
For 45 or more
5" Rigid, up to 70
Pipe to wire diameter
10.55 to 1
In THW insulation
38 fit
In XHHW-2 insulation
45 fit

Before you pull 44

#2 THHN in other 4" conduit

#2 THHN in other Rigid sizes

Other wire sizes in 4" Rigid

Charts