How many #2 THHN fit in 4" Rigid?
442 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)
12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.1158 sq in per wire = 44.50, so 44.
This pull in numbers
- 44 wires fill
- 39.6 % of 4" Rigid
- Limit for three or more
- 40 %
- For 45 or more
- 5" Rigid, up to 70
- Pipe to wire diameter
- 10.55 to 1
- In THW insulation
- 38 fit
- In XHHW-2 insulation
- 45 fit
Before you pull 44
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 44 is the total, not the hots.
- Derating. If all 44 were current-carrying, each would be adjusted to 35 % of its ampacity (Table 310.15(C)(1)): a #2 THHN at 130 A in the 90 °C column becomes 45.5 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#2 THHN in other 4" conduit
| Conduit | Inside area | Most #2 THHN |
|---|---|---|
| Electrical metallic tubing | 14.753 | 51 |
| Intermediate metal conduit | 13.631 | 47 |
| Rigid metal conduit (RMC, GRC) | 12.882 | 44 |
| Rigid PVC conduit, Schedule 40 | 12.554 | 43 |
| Rigid PVC conduit, Schedule 80 | 11.258 | 39 |
| Flexible metal conduit (FMC, Greenfield) | 12.566 | 43 |
| Liquidtight flexible metal conduit (LFMC) | 12.692 | 44 |
#2 THHN in other Rigid sizes
Other wire sizes in 4" Rigid
#8: 140#6: 101#4: 62#3: 53#2: 44#1: 33#1/0: 27#2/0: 23#3/0: 19#4/0: 16250 kcmil: 13300 kcmil: 11350 kcmil: 10500 kcmil: 7