ConduitCount

How many #2 THHN fit in 6" PVC Sch 80?

882 AWG THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 80

25.598 sq in × 40 % = 10.2392 sq in allowed. ÷ 0.1158 sq in per wire = 88.42, so 88.

88 #2 THHN in 6" PVC Sch 80, drawn to scale

This pull in numbers

88 wires fill
39.8 % of 6" PVC Sch 80
Limit for three or more
40 %
For 89 or more
no bigger PVC Sch 80
Pipe to wire diameter
14.87 to 1
In THW insulation
77 fit
In XHHW-2 insulation
89 fit

Before you pull 88

#2 THHN in other 6" conduit

ConduitInside areaMost #2 THHN
Rigid metal conduit (RMC, GRC)29.158100
Rigid PVC conduit, Schedule 4028.56798
Rigid PVC conduit, Schedule 8025.59888

#2 THHN in other PVC Sch 80 sizes

Other wire sizes in 6" PVC Sch 80

Charts