ConduitCount

How many #2 THHN fit in 3-1/2" Rigid?

342 AWG THHN/THWN-2 wires in 3-1/2" Rigid metal conduit (RMC, GRC)

10.010 sq in × 40 % = 4.0040 sq in allowed. ÷ 0.1158 sq in per wire = 34.58, so 34.

34 #2 THHN in 3-1/2" Rigid, drawn to scale

This pull in numbers

34 wires fill
39.3 % of 3-1/2" Rigid
Limit for three or more
40 %
For 35 or more
4" Rigid, up to 44
Pipe to wire diameter
9.30 to 1
In THW insulation
30 fit
In XHHW-2 insulation
35 fit

Before you pull 34

#2 THHN in other 3-1/2" conduit

#2 THHN in other Rigid sizes

Other wire sizes in 3-1/2" Rigid

Charts