ConduitCount

How many 250 kcmil THHN fit in 4" PVC Sch 40?

12250 kcmil THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 40

12.554 sq in × 40 % = 5.0216 sq in allowed. ÷ 0.3970 sq in per wire = 12.65, so 12.

12 250 kcmil THHN in 4" PVC Sch 40, drawn to scale

This pull in numbers

12 wires fill
37.9 % of 4" PVC Sch 40
Limit for three or more
40 %
For 13 or more
5" PVC Sch 40, up to 20
Pipe to wire diameter
5.62 to 1
In THW insulation
11 fit
In XHHW-2 insulation
13 fit

Before you pull 12

250 kcmil THHN in other 4" conduit

250 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 4" PVC Sch 40

Charts