ConduitCount

How many 250 kcmil THHN fit in 3" PVC Sch 40?

7250 kcmil THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 40

7.268 sq in × 40 % = 2.9072 sq in allowed. ÷ 0.3970 sq in per wire = 7.32, so 7.

7 250 kcmil THHN in 3" PVC Sch 40, drawn to scale

This pull in numbers

7 wires fill
38.2 % of 3" PVC Sch 40
Limit for three or more
40 %
For 8 or more
3-1/2" PVC Sch 40, up to 10
Pipe to wire diameter
4.28 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

250 kcmil THHN in other 3" conduit

250 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 3" PVC Sch 40

Charts