ConduitCount

How many #3/0 THHN fit in 2" PVC Sch 40?

53/0 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 40

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.2679 sq in per wire = 4.91, which Note 7 rounds up to 5 because the decimal is 0.8 or more.

5 #3/0 THHN in 2" PVC Sch 40, drawn to scale

This pull in numbers

5 wires fill
40.7 % of 2" PVC Sch 40
Limit for three or more
40 %
For 6 or more
2-1/2" PVC Sch 40, up to 7
Pipe to wire diameter
3.51 to 1
In THW insulation
4 fit
In XHHW-2 insulation
5 fit

Before you pull 5

#3/0 THHN in other 2" conduit

#3/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 2" PVC Sch 40

Charts