ConduitCount

How many #3 THHN fit in 2" PVC Sch 80?

123 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 80

2.874 sq in × 40 % = 1.1496 sq in allowed. ÷ 0.0973 sq in per wire = 11.82, which Note 7 rounds up to 12 because the decimal is 0.8 or more.

12 #3 THHN in 2" PVC Sch 80, drawn to scale

This pull in numbers

12 wires fill
40.6 % of 2" PVC Sch 80
Limit for three or more
40 %
For 13 or more
2-1/2" PVC Sch 80, up to 17
Pipe to wire diameter
5.43 to 1
In THW insulation
10 fit
In XHHW-2 insulation
12 fit

Before you pull 12

#3 THHN in other 2" conduit

#3 THHN in other PVC Sch 80 sizes

Other wire sizes in 2" PVC Sch 80

Charts