ConduitCount

How many #3 THHN fit in 2-1/2" Liquidtight?

203 AWG THHN/THWN-2 wires in 2-1/2" Liquidtight flexible metal conduit (LFMC)

4.881 sq in × 40 % = 1.9524 sq in allowed. ÷ 0.0973 sq in per wire = 20.07, so 20.

20 #3 THHN in 2-1/2" Liquidtight, drawn to scale

This pull in numbers

20 wires fill
39.9 % of 2-1/2" Liquidtight
Limit for three or more
40 %
For 21 or more
3" Liquidtight, up to 30
Pipe to wire diameter
7.08 to 1
In THW insulation
17 fit
In XHHW-2 insulation
20 fit

Before you pull 20

#3 THHN in other 2-1/2" conduit

ConduitInside areaMost #3 THHN
Electrical metallic tubing5.85824
Intermediate metal conduit5.13521
Rigid metal conduit (RMC, GRC)4.86620
Rigid PVC conduit, Schedule 404.69519
Rigid PVC conduit, Schedule 804.11917
Flexible metal conduit (FMC, Greenfield)4.90920
Liquidtight flexible metal conduit (LFMC)4.88120

#3 THHN in other Liquidtight sizes

Other wire sizes in 2-1/2" Liquidtight

Charts