ConduitCount

How many #3 THHN fit in 2" EMT?

133 AWG THHN/THWN-2 wires in 2" Electrical metallic tubing

3.356 sq in × 40 % = 1.3424 sq in allowed. ÷ 0.0973 sq in per wire = 13.80, so 13.

13 #3 THHN in 2" EMT, drawn to scale

This pull in numbers

13 wires fill
37.7 % of 2" EMT
Limit for three or more
40 %
For 14 or more
2-1/2" EMT, up to 24
Pipe to wire diameter
5.87 to 1
In THW insulation
12 fit
In XHHW-2 insulation
14 fit

Before you pull 13

#3 THHN in other 2" conduit

#3 THHN in other EMT sizes

Other wire sizes in 2" EMT

Charts