ConduitCount

How many #3 THHN fit in 3-1/2" PVC Sch 80?

353 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80

8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.0973 sq in per wire = 35.72, so 35.

35 #3 THHN in 3-1/2" PVC Sch 80, drawn to scale

This pull in numbers

35 wires fill
39.2 % of 3-1/2" PVC Sch 80
Limit for three or more
40 %
For 36 or more
4" PVC Sch 80, up to 46
Pipe to wire diameter
9.45 to 1
In THW insulation
30 fit
In XHHW-2 insulation
36 fit

Before you pull 35

#3 THHN in other 3-1/2" conduit

#3 THHN in other PVC Sch 80 sizes

Other wire sizes in 3-1/2" PVC Sch 80

Charts