How many #3 THHN fit in 3-1/2" IMC?

433 AWG THHN/THWN-2 wires in 3-1/2" Intermediate metal conduit

10.584 sq in × 40 % = 4.2336 sq in allowed. ÷ 0.0973 sq in per wire = 43.51, so 43.

43 #3 THHN in 3-1/2" IMC, drawn to scale

This pull in numbers

43 wires fill
39.5 % of 3-1/2" IMC
Limit for three or more
40 %
For 44 or more
4" IMC, up to 56
Pipe to wire diameter
10.43 to 1
In THW insulation
37 fit
In XHHW-2 insulation
44 fit

Before you pull 43

#3 THHN in other 3-1/2" conduit

#3 THHN in other IMC sizes

Other wire sizes in 3-1/2" IMC