How many #3 THHN fit in 3" IMC?

323 AWG THHN/THWN-2 wires in 3" Intermediate metal conduit

7.922 sq in × 40 % = 3.1688 sq in allowed. ÷ 0.0973 sq in per wire = 32.57, so 32.

32 #3 THHN in 3" IMC, drawn to scale

This pull in numbers

32 wires fill
39.3 % of 3" IMC
Limit for three or more
40 %
For 33 or more
3-1/2" IMC, up to 43
Pipe to wire diameter
9.02 to 1
In THW insulation
28 fit
In XHHW-2 insulation
33 fit

Before you pull 32

#3 THHN in other 3" conduit

#3 THHN in other IMC sizes

Other wire sizes in 3" IMC

Charts