ConduitCount

How many #3 THHN fit in 2-1/2" IMC?

213 AWG THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.0973 sq in per wire = 21.11, so 21.

21 #3 THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

21 wires fill
39.8 % of 2-1/2" IMC
Limit for three or more
40 %
For 22 or more
3" IMC, up to 32
Pipe to wire diameter
7.26 to 1
In THW insulation
18 fit
In XHHW-2 insulation
21 fit

Before you pull 21

#3 THHN in other 2-1/2" conduit

#3 THHN in other IMC sizes

Other wire sizes in 2-1/2" IMC