ConduitCount

How many 300 kcmil THHN fit in 2-1/2" Liquidtight?

4300 kcmil THHN/THWN-2 wires in 2-1/2" Liquidtight flexible metal conduit (LFMC)

4.881 sq in × 40 % = 1.9524 sq in allowed. ÷ 0.4608 sq in per wire = 4.24, so 4.

4 300 kcmil THHN in 2-1/2" Liquidtight, drawn to scale

This pull in numbers

4 wires fill
37.8 % of 2-1/2" Liquidtight
Limit for three or more
40 %
For 5 or more
3" Liquidtight, up to 6
Pipe to wire diameter
3.25 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

Before you pull 4

300 kcmil THHN in other 2-1/2" conduit

ConduitInside areaMost 300 kcmil THHN
Electrical metallic tubing5.8585
Intermediate metal conduit5.1354
Rigid metal conduit (RMC, GRC)4.8664
Rigid PVC conduit, Schedule 404.6954
Rigid PVC conduit, Schedule 804.1193
Flexible metal conduit (FMC, Greenfield)4.9094
Liquidtight flexible metal conduit (LFMC)4.8814

300 kcmil THHN in other Liquidtight sizes

Other wire sizes in 2-1/2" Liquidtight

Charts