ConduitCount

How many 350 kcmil THHN fit in 2-1/2" Liquidtight?

3350 kcmil THHN/THWN-2 wires in 2-1/2" Liquidtight flexible metal conduit (LFMC)

4.881 sq in × 40 % = 1.9524 sq in allowed. ÷ 0.5242 sq in per wire = 3.72, so 3.

3 350 kcmil THHN in 2-1/2" Liquidtight, drawn to scale

This pull in numbers

3 wires fill
32.2 % of 2-1/2" Liquidtight
Limit for three or more
40 %
For 4 or more
3" Liquidtight, up to 5
Pipe to wire diameter
3.05 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 3.05 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 3

350 kcmil THHN in other 2-1/2" conduit

ConduitInside areaMost 350 kcmil THHN
Electrical metallic tubing5.8584
Intermediate metal conduit5.1354
Rigid metal conduit (RMC, GRC)4.8663
Rigid PVC conduit, Schedule 404.6953
Rigid PVC conduit, Schedule 804.1193
Flexible metal conduit (FMC, Greenfield)4.9093
Liquidtight flexible metal conduit (LFMC)4.8813

350 kcmil THHN in other Liquidtight sizes

Other wire sizes in 2-1/2" Liquidtight

Charts