ConduitCount

How many #2 THHN fit in 2-1/2" Liquidtight?

172 AWG THHN/THWN-2 wires in 2-1/2" Liquidtight flexible metal conduit (LFMC)

4.881 sq in × 40 % = 1.9524 sq in allowed. ÷ 0.1158 sq in per wire = 16.86, which Note 7 rounds up to 17 because the decimal is 0.8 or more.

17 #2 THHN in 2-1/2" Liquidtight, drawn to scale

This pull in numbers

17 wires fill
40.3 % of 2-1/2" Liquidtight
Limit for three or more
40 %
For 18 or more
3" Liquidtight, up to 26
Pipe to wire diameter
6.49 to 1
In THW insulation
14 fit
In XHHW-2 insulation
17 fit

Before you pull 17

#2 THHN in other 2-1/2" conduit

ConduitInside areaMost #2 THHN
Electrical metallic tubing5.85820
Intermediate metal conduit5.13517
Rigid metal conduit (RMC, GRC)4.86617
Rigid PVC conduit, Schedule 404.69516
Rigid PVC conduit, Schedule 804.11914
Flexible metal conduit (FMC, Greenfield)4.90917
Liquidtight flexible metal conduit (LFMC)4.88117

#2 THHN in other Liquidtight sizes

Other wire sizes in 2-1/2" Liquidtight

Charts