ConduitCount

How many #1 THHN fit in 2-1/2" Liquidtight?

121 AWG THHN/THWN-2 wires in 2-1/2" Liquidtight flexible metal conduit (LFMC)

4.881 sq in × 40 % = 1.9524 sq in allowed. ÷ 0.1562 sq in per wire = 12.50, so 12.

12 #1 THHN in 2-1/2" Liquidtight, drawn to scale

This pull in numbers

12 wires fill
38.4 % of 2-1/2" Liquidtight
Limit for three or more
40 %
For 13 or more
3" Liquidtight, up to 19
Pipe to wire diameter
5.59 to 1
In THW insulation
10 fit
In XHHW-2 insulation
12 fit

Before you pull 12

#1 THHN in other 2-1/2" conduit

ConduitInside areaMost #1 THHN
Electrical metallic tubing5.85815
Intermediate metal conduit5.13513
Rigid metal conduit (RMC, GRC)4.86612
Rigid PVC conduit, Schedule 404.69512
Rigid PVC conduit, Schedule 804.11910
Flexible metal conduit (FMC, Greenfield)4.90912
Liquidtight flexible metal conduit (LFMC)4.88112

#1 THHN in other Liquidtight sizes

Other wire sizes in 2-1/2" Liquidtight

Charts