ConduitCount

How many 350 kcmil THHN fit in 2-1/2" PVC Sch 80?

3350 kcmil THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 80

4.119 sq in × 40 % = 1.6476 sq in allowed. ÷ 0.5242 sq in per wire = 3.14, so 3.

3 350 kcmil THHN in 2-1/2" PVC Sch 80, drawn to scale

This pull in numbers

3 wires fill
38.2 % of 2-1/2" PVC Sch 80
Limit for three or more
40 %
For 4 or more
3" PVC Sch 80, up to 5
Pipe to wire diameter
2.80 to 1
In THW insulation
2 fit
In XHHW-2 insulation
3 fit

The pipe is 2.80 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 3

350 kcmil THHN in other 2-1/2" conduit

350 kcmil THHN in other PVC Sch 80 sizes

Other wire sizes in 2-1/2" PVC Sch 80

Charts