ConduitCount

How many 350 kcmil THHN fit in 4" EMT?

11350 kcmil THHN/THWN-2 wires in 4" Electrical metallic tubing

14.753 sq in × 40 % = 5.9012 sq in allowed. ÷ 0.5242 sq in per wire = 11.26, so 11.

11 350 kcmil THHN in 4" EMT, drawn to scale

This pull in numbers

11 wires fill
39.1 % of 4" EMT
Limit for three or more
40 %
For 12 or more
no bigger EMT
Pipe to wire diameter
5.30 to 1
In THW insulation
10 fit
In XHHW-2 insulation
11 fit

Before you pull 11

350 kcmil THHN in other 4" conduit

350 kcmil THHN in other EMT sizes

Other wire sizes in 4" EMT

Charts