ConduitCount

How many 350 kcmil THHN fit in 4" Rigid?

10350 kcmil THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.5242 sq in per wire = 9.83, which Note 7 rounds up to 10 because the decimal is 0.8 or more.

10 350 kcmil THHN in 4" Rigid, drawn to scale

This pull in numbers

10 wires fill
40.7 % of 4" Rigid
Limit for three or more
40 %
For 11 or more
5" Rigid, up to 15
Pipe to wire diameter
4.96 to 1
In THW insulation
8 fit
In XHHW-2 insulation
10 fit

Before you pull 10

350 kcmil THHN in other 4" conduit

350 kcmil THHN in other Rigid sizes

Other wire sizes in 4" Rigid

Charts