ConduitCount

How many #6 THHN fit in 4" EMT?

1166 AWG THHN/THWN-2 wires in 4" Electrical metallic tubing

14.753 sq in × 40 % = 5.9012 sq in allowed. ÷ 0.0507 sq in per wire = 116.39, so 116.

116 #6 THHN in 4" EMT, drawn to scale

This pull in numbers

116 wires fill
39.9 % of 4" EMT
Limit for three or more
40 %
For 117 or more
no bigger EMT
Pipe to wire diameter
17.06 to 1
In THW insulation
81 fit
In XHHW-2 insulation
100 fit

Before you pull 116

#6 THHN in other 4" conduit

#6 THHN in other EMT sizes

Other wire sizes in 4" EMT

Charts