184/0 AWG THHN/THWN-2 wires in 4" Electrical metallic tubing

14.753 sq in × 40 % = 5.9012 sq in allowed. ÷ 0.3237 sq in per wire = 18.23, so 18.

18 #4/0 THHN in 4" EMT, drawn to scale

This pull in numbers

18 wires fill
39.5 % of 4" EMT
Limit for three or more
40 %
For 19 or more
no bigger EMT
Pipe to wire diameter
6.75 to 1
In THW insulation
16 fit
In XHHW-2 insulation
18 fit