How many 350 kcmil THHN fit in 4" IMC?
10350 kcmil THHN/THWN-2 wires in 4" Intermediate metal conduit
13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.5242 sq in per wire = 10.40, so 10.
This pull in numbers
- 10 wires fill
- 38.5 % of 4" IMC
- Limit for three or more
- 40 %
- For 11 or more
- no bigger IMC
- Pipe to wire diameter
- 5.10 to 1
- In THW insulation
- 9 fit
- In XHHW-2 insulation
- 10 fit
Before you pull 10
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 10 is the total, not the hots.
- Derating. If all 10 were current-carrying, each would be adjusted to 50 % of its ampacity (Table 310.15(C)(1)): a 350 kcmil THHN at 350 A in the 90 °C column becomes 175 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
350 kcmil THHN in other 4" conduit
| Conduit | Inside area | Most 350 kcmil THHN |
|---|---|---|
| Electrical metallic tubing | 14.753 | 11 |
| Intermediate metal conduit | 13.631 | 10 |
| Rigid metal conduit (RMC, GRC) | 12.882 | 10 |
| Rigid PVC conduit, Schedule 40 | 12.554 | 9 |
| Rigid PVC conduit, Schedule 80 | 11.258 | 8 |
| Flexible metal conduit (FMC, Greenfield) | 12.566 | 9 |
| Liquidtight flexible metal conduit (LFMC) | 12.692 | 9 |
350 kcmil THHN in other IMC sizes
Other wire sizes in 4" IMC
#8: 149#6: 107#4: 66#3: 56#2: 47#1: 35#1/0: 29#2/0: 24#3/0: 20#4/0: 17250 kcmil: 13300 kcmil: 12350 kcmil: 10500 kcmil: 7