ConduitCount

How many #1/0 THHN fit in 4" EMT?

321/0 AWG THHN/THWN-2 wires in 4" Electrical metallic tubing

14.753 sq in × 40 % = 5.9012 sq in allowed. ÷ 0.1855 sq in per wire = 31.81, which Note 7 rounds up to 32 because the decimal is 0.8 or more.

32 #1/0 THHN in 4" EMT, drawn to scale

This pull in numbers

32 wires fill
40.2 % of 4" EMT
Limit for three or more
40 %
For 33 or more
no bigger EMT
Pipe to wire diameter
8.92 to 1
In THW insulation
26 fit
In XHHW-2 insulation
32 fit

Before you pull 32

#1/0 THHN in other 4" conduit

#1/0 THHN in other EMT sizes

Other wire sizes in 4" EMT

Charts