ConduitCount

How many #4/0 THHN fit in 3" IMC?

94/0 AWG THHN/THWN-2 wires in 3" Intermediate metal conduit

7.922 sq in × 40 % = 3.1688 sq in allowed. ÷ 0.3237 sq in per wire = 9.79, so 9.

9 #4/0 THHN in 3" IMC, drawn to scale

This pull in numbers

9 wires fill
36.8 % of 3" IMC
Limit for three or more
40 %
For 10 or more
3-1/2" IMC, up to 13
Pipe to wire diameter
4.95 to 1
In THW insulation
8 fit
In XHHW-2 insulation
10 fit

Before you pull 9

#4/0 THHN in other 3" conduit

#4/0 THHN in other IMC sizes

Other wire sizes in 3" IMC

Charts