ConduitCount

How many #4/0 THHN fit in 3-1/2" IMC?

134/0 AWG THHN/THWN-2 wires in 3-1/2" Intermediate metal conduit

10.584 sq in × 40 % = 4.2336 sq in allowed. ÷ 0.3237 sq in per wire = 13.08, so 13.

13 #4/0 THHN in 3-1/2" IMC, drawn to scale

This pull in numbers

13 wires fill
39.8 % of 3-1/2" IMC
Limit for three or more
40 %
For 14 or more
4" IMC, up to 17
Pipe to wire diameter
5.72 to 1
In THW insulation
11 fit
In XHHW-2 insulation
13 fit

Before you pull 13

#4/0 THHN in other 3-1/2" conduit

#4/0 THHN in other IMC sizes

Other wire sizes in 3-1/2" IMC

Charts