ConduitCount

How many #4/0 THHN fit in 2" IMC?

44/0 AWG THHN/THWN-2 wires in 2" Intermediate metal conduit

3.630 sq in × 40 % = 1.4520 sq in allowed. ÷ 0.3237 sq in per wire = 4.49, so 4.

4 #4/0 THHN in 2" IMC, drawn to scale

This pull in numbers

4 wires fill
35.7 % of 2" IMC
Limit for three or more
40 %
For 5 or more
2-1/2" IMC, up to 6
Pipe to wire diameter
3.35 to 1
In THW insulation
4 fit
In XHHW-2 insulation
4 fit

Before you pull 4

#4/0 THHN in other 2" conduit

#4/0 THHN in other IMC sizes

Other wire sizes in 2" IMC

Charts