ConduitCount

How many #4 THHN fit in 4" PVC Sch 40?

614 AWG THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 40

12.554 sq in × 40 % = 5.0216 sq in allowed. ÷ 0.0824 sq in per wire = 60.94, which Note 7 rounds up to 61 because the decimal is 0.8 or more.

61 #4 THHN in 4" PVC Sch 40, drawn to scale

This pull in numbers

61 wires fill
40.0 % of 4" PVC Sch 40
Limit for three or more
40 %
For 62 or more
5" PVC Sch 40, up to 96
Pipe to wire diameter
12.34 to 1
In THW insulation
51 fit
In XHHW-2 insulation
61 fit

Before you pull 61

#4 THHN in other 4" conduit

#4 THHN in other PVC Sch 40 sizes

Other wire sizes in 4" PVC Sch 40

Charts