ConduitCount

How many #2 THHN fit in 4" PVC Sch 40?

432 AWG THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 40

12.554 sq in × 40 % = 5.0216 sq in allowed. ÷ 0.1158 sq in per wire = 43.36, so 43.

43 #2 THHN in 4" PVC Sch 40, drawn to scale

This pull in numbers

43 wires fill
39.7 % of 4" PVC Sch 40
Limit for three or more
40 %
For 44 or more
5" PVC Sch 40, up to 68
Pipe to wire diameter
10.41 to 1
In THW insulation
37 fit
In XHHW-2 insulation
44 fit

Before you pull 43

#2 THHN in other 4" conduit

#2 THHN in other PVC Sch 40 sizes

Other wire sizes in 4" PVC Sch 40

Charts