ConduitCount

How many #4 THHN fit in 3-1/2" PVC Sch 40?

474 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 40

9.737 sq in × 40 % = 3.8948 sq in allowed. ÷ 0.0824 sq in per wire = 47.27, so 47.

47 #4 THHN in 3-1/2" PVC Sch 40, drawn to scale

This pull in numbers

47 wires fill
39.8 % of 3-1/2" PVC Sch 40
Limit for three or more
40 %
For 48 or more
4" PVC Sch 40, up to 61
Pipe to wire diameter
10.87 to 1
In THW insulation
40 fit
In XHHW-2 insulation
48 fit

Before you pull 47

#4 THHN in other 3-1/2" conduit

#4 THHN in other PVC Sch 40 sizes

Other wire sizes in 3-1/2" PVC Sch 40

Charts