How many #1/0 THHN fit in 1-1/4" PVC Sch 40?

31/0 AWG THHN/THWN-2 wires in 1-1/4" Rigid PVC conduit, Schedule 40

1.453 sq in × 40 % = 0.5812 sq in allowed. ÷ 0.1855 sq in per wire = 3.13, so 3.

3 #1/0 THHN in 1-1/4" PVC Sch 40, drawn to scale

This pull in numbers

3 wires fill
38.3 % of 1-1/4" PVC Sch 40
Limit for three or more
40 %
For 4 or more
1-1/2" PVC Sch 40, up to 4
Pipe to wire diameter
2.80 to 1
In THW insulation
2 fit
In XHHW-2 insulation
3 fit

Before you pull 3

#1/0 THHN in other 1-1/4" conduit

#1/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 1-1/4" PVC Sch 40

Charts