How many #14 THHN fit in 1-1/4" PVC Sch 40?

6014 AWG THHN/THWN-2 wires in 1-1/4" Rigid PVC conduit, Schedule 40

1.453 sq in × 40 % = 0.5812 sq in allowed. ÷ 0.0097 sq in per wire = 59.92, which Note 7 rounds up to 60 because the decimal is 0.8 or more.

60 #14 THHN in 1-1/4" PVC Sch 40, drawn to scale

This pull in numbers

60 wires fill
40.1 % of 1-1/4" PVC Sch 40
Limit for three or more
40 %
For 61 or more
1-1/2" PVC Sch 40, up to 82
Pipe to wire diameter
12.25 to 1
In THW insulation
42 fit
In XHHW-2 insulation
42 fit

Before you pull 60

#14 THHN in other 1-1/4" conduit

#14 THHN in other PVC Sch 40 sizes

Other wire sizes in 1-1/4" PVC Sch 40