How many 500 kcmil THHN fit in 3-1/2" PVC Sch 80?

5500 kcmil THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80

8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.7073 sq in per wire = 4.91, which Note 7 rounds up to 5 because the decimal is 0.8 or more.

5 500 kcmil THHN in 3-1/2" PVC Sch 80, drawn to scale

This pull in numbers

5 wires fill
40.7 % of 3-1/2" PVC Sch 80
Limit for three or more
40 %
For 6 or more
4" PVC Sch 80, up to 6
Pipe to wire diameter
3.50 to 1
In THW insulation
4 fit
In XHHW-2 insulation
5 fit

Before you pull 5

500 kcmil THHN in other 3-1/2" conduit

500 kcmil THHN in other PVC Sch 80 sizes

Other wire sizes in 3-1/2" PVC Sch 80