ConduitCount

How many #6 THHN fit in 1-1/2" Rigid?

166 AWG THHN/THWN-2 wires in 1-1/2" Rigid metal conduit (RMC, GRC)

2.071 sq in × 40 % = 0.8284 sq in allowed. ÷ 0.0507 sq in per wire = 16.34, so 16.

16 #6 THHN in 1-1/2" Rigid, drawn to scale

This pull in numbers

16 wires fill
39.2 % of 1-1/2" Rigid
Limit for three or more
40 %
For 17 or more
2" Rigid, up to 27
Pipe to wire diameter
6.39 to 1
In THW insulation
11 fit
In XHHW-2 insulation
14 fit

Before you pull 16

#6 THHN in other 1-1/2" conduit

#6 THHN in other Rigid sizes

Other wire sizes in 1-1/2" Rigid

Charts