ConduitCount

How many #6 THHN fit in 1-1/2" PVC Sch 80?

136 AWG THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 80

1.711 sq in × 40 % = 0.6844 sq in allowed. ÷ 0.0507 sq in per wire = 13.50, so 13.

13 #6 THHN in 1-1/2" PVC Sch 80, drawn to scale

This pull in numbers

13 wires fill
38.5 % of 1-1/2" PVC Sch 80
Limit for three or more
40 %
For 14 or more
2" PVC Sch 80, up to 22
Pipe to wire diameter
5.81 to 1
In THW insulation
9 fit
In XHHW-2 insulation
11 fit

Before you pull 13

#6 THHN in other 1-1/2" conduit

#6 THHN in other PVC Sch 80 sizes

Other wire sizes in 1-1/2" PVC Sch 80

Charts