ConduitCount

How many #8 THHN fit in 3-1/2" PVC Sch 80?

958 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80

8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.0366 sq in per wire = 94.95, which Note 7 rounds up to 95 because the decimal is 0.8 or more.

95 #8 THHN in 3-1/2" PVC Sch 80, drawn to scale

This pull in numbers

95 wires fill
40.0 % of 3-1/2" PVC Sch 80
Limit for three or more
40 %
For 96 or more
4" PVC Sch 80, up to 123
Pipe to wire diameter
15.40 to 1
In THW insulation
79 fit
In XHHW-2 insulation
79 fit

Before you pull 95

#8 THHN in other 3-1/2" conduit

#8 THHN in other PVC Sch 80 sizes

Other wire sizes in 3-1/2" PVC Sch 80

Charts