ConduitCount

How many #8 THHN fit in 3-1/2" PVC Sch 40?

1068 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 40

9.737 sq in × 40 % = 3.8948 sq in allowed. ÷ 0.0366 sq in per wire = 106.42, so 106.

106 #8 THHN in 3-1/2" PVC Sch 40, drawn to scale

This pull in numbers

106 wires fill
39.8 % of 3-1/2" PVC Sch 40
Limit for three or more
40 %
For 107 or more
4" PVC Sch 40, up to 137
Pipe to wire diameter
16.30 to 1
In THW insulation
89 fit
In XHHW-2 insulation
89 fit

Before you pull 106

#8 THHN in other 3-1/2" conduit

#8 THHN in other PVC Sch 40 sizes

Other wire sizes in 3-1/2" PVC Sch 40

Charts