How many #8 THHN fit in 3" PVC Sch 40?

798 AWG THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 40

7.268 sq in × 40 % = 2.9072 sq in allowed. ÷ 0.0366 sq in per wire = 79.43, so 79.

79 #8 THHN in 3" PVC Sch 40, drawn to scale

This pull in numbers

79 wires fill
39.8 % of 3" PVC Sch 40
Limit for three or more
40 %
For 80 or more
3-1/2" PVC Sch 40, up to 106
Pipe to wire diameter
14.08 to 1
In THW insulation
66 fit
In XHHW-2 insulation
66 fit