ConduitCount

How many #8 THHN fit in 2" PVC Sch 40?

368 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 40

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.0366 sq in per wire = 35.97, which Note 7 rounds up to 36 because the decimal is 0.8 or more.

36 #8 THHN in 2" PVC Sch 40, drawn to scale

This pull in numbers

36 wires fill
40.0 % of 2" PVC Sch 40
Limit for three or more
40 %
For 37 or more
2-1/2" PVC Sch 40, up to 51
Pipe to wire diameter
9.48 to 1
In THW insulation
30 fit
In XHHW-2 insulation
30 fit

Before you pull 36

#8 THHN in other 2" conduit

#8 THHN in other PVC Sch 40 sizes

Other wire sizes in 2" PVC Sch 40

Charts