How many #1/0 THHN fit in 3" PVC Sch 40?
151/0 AWG THHN/THWN-2 wires in 3" Rigid PVC conduit, Schedule 40
7.268 sq in × 40 % = 2.9072 sq in allowed. ÷ 0.1855 sq in per wire = 15.67, so 15.
This pull in numbers
- 15 wires fill
- 38.3 % of 3" PVC Sch 40
- Limit for three or more
- 40 %
- For 16 or more
- 3-1/2" PVC Sch 40, up to 21
- Pipe to wire diameter
- 6.26 to 1
- In THW insulation
- 13 fit
- In XHHW-2 insulation
- 16 fit
Before you pull 15
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 15 is the total, not the hots.
- Derating. If all 15 were current-carrying, each would be adjusted to 50 % of its ampacity (Table 310.15(C)(1)): a #1/0 THHN at 170 A in the 90 °C column becomes 85 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#1/0 THHN in other 3" conduit
| Conduit | Inside area | Most #1/0 THHN |
|---|---|---|
| Electrical metallic tubing | 8.846 | 19 |
| Intermediate metal conduit | 7.922 | 17 |
| Rigid metal conduit (RMC, GRC) | 7.499 | 16 |
| Rigid PVC conduit, Schedule 40 | 7.268 | 15 |
| Rigid PVC conduit, Schedule 80 | 6.442 | 14 |
| Flexible metal conduit (FMC, Greenfield) | 7.069 | 15 |
| Liquidtight flexible metal conduit (LFMC) | 7.475 | 16 |
#1/0 THHN in other PVC Sch 40 sizes
Other wire sizes in 3" PVC Sch 40
#10: 137#8: 79#6: 57#4: 35#3: 30#2: 25#1: 18#1/0: 15#2/0: 13#3/0: 11#4/0: 9250 kcmil: 7300 kcmil: 6350 kcmil: 5500 kcmil: 4