ConduitCount

How many #8 THHN fit in 2" PVC Sch 80?

318 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 80

2.874 sq in × 40 % = 1.1496 sq in allowed. ÷ 0.0366 sq in per wire = 31.41, so 31.

31 #8 THHN in 2" PVC Sch 80, drawn to scale

This pull in numbers

31 wires fill
39.5 % of 2" PVC Sch 80
Limit for three or more
40 %
For 32 or more
2-1/2" PVC Sch 80, up to 45
Pipe to wire diameter
8.86 to 1
In THW insulation
26 fit
In XHHW-2 insulation
26 fit

Before you pull 31

#8 THHN in other 2" conduit

#8 THHN in other PVC Sch 80 sizes

Other wire sizes in 2" PVC Sch 80

Charts