ConduitCount

How many #2 THHN fit in 2" PVC Sch 80?

102 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 80

2.874 sq in × 40 % = 1.1496 sq in allowed. ÷ 0.1158 sq in per wire = 9.93, which Note 7 rounds up to 10 because the decimal is 0.8 or more.

10 #2 THHN in 2" PVC Sch 80, drawn to scale

This pull in numbers

10 wires fill
40.3 % of 2" PVC Sch 80
Limit for three or more
40 %
For 11 or more
2-1/2" PVC Sch 80, up to 14
Pipe to wire diameter
4.98 to 1
In THW insulation
8 fit
In XHHW-2 insulation
10 fit

Before you pull 10

#2 THHN in other 2" conduit

#2 THHN in other PVC Sch 80 sizes

Other wire sizes in 2" PVC Sch 80

Charts