ConduitCount

How many #4/0 THHN fit in 2" PVC Sch 80?

34/0 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 80

2.874 sq in × 40 % = 1.1496 sq in allowed. ÷ 0.3237 sq in per wire = 3.55, so 3.

3 #4/0 THHN in 2" PVC Sch 80, drawn to scale

This pull in numbers

3 wires fill
33.8 % of 2" PVC Sch 80
Limit for three or more
40 %
For 4 or more
2-1/2" PVC Sch 80, up to 5
Pipe to wire diameter
2.98 to 1
In THW insulation
3 fit
In XHHW-2 insulation
3 fit

The pipe is 2.98 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 3

#4/0 THHN in other 2" conduit

#4/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 2" PVC Sch 80

Charts