ConduitCount

How many 500 kcmil THHN fit in 6" PVC Sch 80?

14500 kcmil THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 80

25.598 sq in × 40 % = 10.2392 sq in allowed. ÷ 0.7073 sq in per wire = 14.48, so 14.

14 500 kcmil THHN in 6" PVC Sch 80, drawn to scale

This pull in numbers

14 wires fill
38.7 % of 6" PVC Sch 80
Limit for three or more
40 %
For 15 or more
no bigger PVC Sch 80
Pipe to wire diameter
6.02 to 1
In THW insulation
13 fit
In XHHW-2 insulation
14 fit

Before you pull 14

500 kcmil THHN in other 6" conduit

ConduitInside areaMost 500 kcmil THHN
Rigid metal conduit (RMC, GRC)29.15816
Rigid PVC conduit, Schedule 4028.56716
Rigid PVC conduit, Schedule 8025.59814

500 kcmil THHN in other PVC Sch 80 sizes

Other wire sizes in 6" PVC Sch 80

Charts