How many #2/0 THHN fit in 6" PVC Sch 80?

462/0 AWG THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 80

25.598 sq in × 40 % = 10.2392 sq in allowed. ÷ 0.2223 sq in per wire = 46.06, so 46.

46 #2/0 THHN in 6" PVC Sch 80, drawn to scale

This pull in numbers

46 wires fill
39.9 % of 6" PVC Sch 80
Limit for three or more
40 %
For 47 or more
no bigger PVC Sch 80
Pipe to wire diameter
10.73 to 1
In THW insulation
39 fit
In XHHW-2 insulation
46 fit

Before you pull 46

#2/0 THHN in other 6" conduit

ConduitInside areaMost #2/0 THHN
Rigid metal conduit (RMC, GRC)29.15852
Rigid PVC conduit, Schedule 4028.56751
Rigid PVC conduit, Schedule 8025.59846

#2/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 6" PVC Sch 80

Charts