ConduitCount

How many #4/0 THHN fit in 6" PVC Sch 80?

314/0 AWG THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 80

25.598 sq in × 40 % = 10.2392 sq in allowed. ÷ 0.3237 sq in per wire = 31.63, so 31.

31 #4/0 THHN in 6" PVC Sch 80, drawn to scale

This pull in numbers

31 wires fill
39.2 % of 6" PVC Sch 80
Limit for three or more
40 %
For 32 or more
no bigger PVC Sch 80
Pipe to wire diameter
8.89 to 1
In THW insulation
27 fit
In XHHW-2 insulation
32 fit

Before you pull 31

#4/0 THHN in other 6" conduit

ConduitInside areaMost #4/0 THHN
Rigid metal conduit (RMC, GRC)29.15836
Rigid PVC conduit, Schedule 4028.56735
Rigid PVC conduit, Schedule 8025.59831

#4/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 6" PVC Sch 80

Charts