ConduitCount

How many #3/0 THHN fit in 6" PVC Sch 80?

383/0 AWG THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 80

25.598 sq in × 40 % = 10.2392 sq in allowed. ÷ 0.2679 sq in per wire = 38.22, so 38.

38 #3/0 THHN in 6" PVC Sch 80, drawn to scale

This pull in numbers

38 wires fill
39.8 % of 6" PVC Sch 80
Limit for three or more
40 %
For 39 or more
no bigger PVC Sch 80
Pipe to wire diameter
9.78 to 1
In THW insulation
33 fit
In XHHW-2 insulation
38 fit

Before you pull 38

#3/0 THHN in other 6" conduit

ConduitInside areaMost #3/0 THHN
Rigid metal conduit (RMC, GRC)29.15843
Rigid PVC conduit, Schedule 4028.56742
Rigid PVC conduit, Schedule 8025.59838

#3/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 6" PVC Sch 80

Charts