651 AWG THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 80

25.598 sq in × 40 % = 10.2392 sq in allowed. ÷ 0.1562 sq in per wire = 65.55, so 65.

65 #1 THHN in 6" PVC Sch 80, drawn to scale

This pull in numbers

65 wires fill
39.7 % of 6" PVC Sch 80
Limit for three or more
40 %
For 66 or more
no bigger PVC Sch 80
Pipe to wire diameter
12.80 to 1
In THW insulation
54 fit
In XHHW-2 insulation
66 fit

Before you pull 65

#1 THHN in other 6" conduit

ConduitInside areaMost #1 THHN
Rigid metal conduit (RMC, GRC)29.15874
Rigid PVC conduit, Schedule 4028.56773
Rigid PVC conduit, Schedule 8025.59865

#1 THHN in other PVC Sch 80 sizes

Other wire sizes in 6" PVC Sch 80