ConduitCount

How many #1/0 THHN fit in 6" PVC Sch 80?

551/0 AWG THHN/THWN-2 wires in 6" Rigid PVC conduit, Schedule 80

25.598 sq in × 40 % = 10.2392 sq in allowed. ÷ 0.1855 sq in per wire = 55.20, so 55.

55 #1/0 THHN in 6" PVC Sch 80, drawn to scale

This pull in numbers

55 wires fill
39.9 % of 6" PVC Sch 80
Limit for three or more
40 %
For 56 or more
no bigger PVC Sch 80
Pipe to wire diameter
11.75 to 1
In THW insulation
46 fit
In XHHW-2 insulation
56 fit

Before you pull 55

#1/0 THHN in other 6" conduit

ConduitInside areaMost #1/0 THHN
Rigid metal conduit (RMC, GRC)29.15863
Rigid PVC conduit, Schedule 4028.56761
Rigid PVC conduit, Schedule 8025.59855

#1/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 6" PVC Sch 80

Charts