ConduitCount

How many #1/0 THHN fit in 3" Rigid?

161/0 AWG THHN/THWN-2 wires in 3" Rigid metal conduit (RMC, GRC)

7.499 sq in × 40 % = 2.9996 sq in allowed. ÷ 0.1855 sq in per wire = 16.17, so 16.

16 #1/0 THHN in 3" Rigid, drawn to scale

This pull in numbers

16 wires fill
39.6 % of 3" Rigid
Limit for three or more
40 %
For 17 or more
3-1/2" Rigid, up to 21
Pipe to wire diameter
6.36 to 1
In THW insulation
13 fit
In XHHW-2 insulation
16 fit

Before you pull 16

#1/0 THHN in other 3" conduit

#1/0 THHN in other Rigid sizes

Other wire sizes in 3" Rigid

Charts